– Suitable primary control must be used to provide safe-start check, safety lockout, load switching and other functions required in flame safeguard systems.
– Three LEDs to indicate power, flame and alarm.
– Access for external electrical voltage checks.
– Nonvolatile memory.
– Shutter drive output.
– Compatible with existing Honeywell flame detectors.
– Application Flame Switch
– Required Components Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier.
– Frequency 60 Hz (±10%).
– Vibration 0.5 G environment.
– Ambient Temperature Range (C) -40 ºC to +60 ºC.
– Dimensions (mm) 127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase.
– Two SPDT outputs.
– Rated Voltage
EC7823A1004 220 to 240 Vac (+10, -15%).
Rm7823A1016 120 Vac (+10, -15%).